0191 5166636 enquiries@ht-uk.com

  

Every pipe or vessel is subject to heat loss when its temperature is greater than ambient temperature. Thermal insulation reduces the rate of heat loss but does not eliminate it. Trace heating maintains the temperature above freezing by balancing heat lost with heat supplied.

 Even in buildings -

Where water storage is likely to be subject to temperatures below freezing, lagging and heating maybe required.

In areas that, under normal circumstances, have ambient temperatures well above freezing then lagging and trace heating will not be required. In these instances it is the responsibility of the occupier to ensure that the ambient temperature within the building is always kept above freezing.

This is particularly important if the property is left unattended for a long period of time in the winter and we would advise that the heating is left on a ‘frost' setting whilst unoccupied.

 

The Need:  Freeze Protection to Fire Sprinkler Pipework

 

RC38 Fire Protection Association recommends the following:

 

Areas subject to freezing Many industrial premises have areas which could be subject to freezing temperatures, for example:

(a)unheated or inadequately heated buildings;
(b)parts of heated buildings exposed to frost, such as ceiling voids or near open doors such as loading bays;
(c)chillers and cold rooms; (d) external pipelines from a remote mains water supply or pump house to a sprinklered building;

(d) the pump house (BS EN 12845, Clause 10.9.2, requires that diesel engines be maintained above  5°C for ease for ease of starting);

(e) areas normally heated but temporarily unheated during out-of-work hours, weekends or winter holidays;

 

1.3 Main frost protection methods

The methods available for protecting areas and water-filled equipment from freezing are:

(a)maintaining adequate heating throughout the building (preferred option, where possible); or
(b)providing localised heating and/or trace heating and lagging to pipes, valves, tanks and ancillary equipment; or (c) using a dry sprinkler pipe or alternate wet/dry sprinkler pipe installation; or (d) using dry drop    sprinklers.

 

BS EN 12845, Clause 11.1.2.2

Duplication of heating elements BS EN 12845, Clause 11.1.2.2, requires that there shall be duplicate heating elements to protect pipework. Each of the elements should be capable of maintaining the pipework at the minimum temperature and each trace-heating circuit should be separately switched and monitored.

Specifications:

 

 

OurSolution:

•Flexible ConstantWattage cut to length heating cable
•Simple terminations
•Automatic control systemin accordance with BSEN 12845
•All fixing requirements

 

Our Systems offer:

All lines should be double traced (one live one standby)

•Automatic Power monitoring for both Primary & Secondary circuits
•Automatic changeover from Primary to Secondary Circuit
•Removable Gear Tray - only 2 screws
•30 watt- 3000 watt power range
•Sensor Circuit monitoring for both O/C And S/C
•Automatic calibration for both Primary and Secondary Circuits
•1 Set of Fault CHO contacts - failsafe
•Internal Fault Buzzer
•LED Bar Display for Sensor Temperature
•Manual Test mode switch
•Primary & Secondary Circuit Heating Status LED’s
•16 amp MCB output protection
•Plastic enclosure to IP55
•Complies with the requirements for BS EN 12845/LPC/FPA(RC38) regulations

Temperature Sensor Assembly Supplied