0191 5166636 enquiries@ht-uk.com

Typical applications are frost protection, temperature maintenance and heat-up in pipes, tanks, vessels or surfaces. The electric trace heating system HSB offers the optimum solution for Zone 1, 2, 21 and 22 as well as Class I Div 2, Class II and III. The self-limiting heating tape HSB is available with various nominal power ratings from 10 W/m to 60 W/m at 10 °C. The outer insulation jacket is made of fluoropolymer for special applications which require chemical resistance and mechanical strength. Dependant on the start-up temperature, the start-up current and the supply voltage a maximum heating circuit length of 235 m is possible.

Specifications:

HSB System overview

  • Self-limiting parallel heating tape HSB
  • Heat shrink technology or silicone cold applied technology or pluggable system PLEXO TCS connection and termination
  • Junction box made of polyester, stainless steel and aluminium
  • Optional: mechanical or electronic thermostats or control systems

Ambient temperature

  • Installation also in Ex-area, maximum admissible work-piece temperatures of
  • +120 °C (switched-on) and
  • +200 °C (switched-off)

Features

  • Simple project planning of heating circuits
  • Self-limiting, without overheating while overlapping
  • Limiter is not required
  • Easy installation due to on-site assembly
  • Certificate for the system according to IEC/EN 60079-30-1 and CSA C22.2 No.130-03
  • Junction boxes made of polyester, stainless steel and aluminium available
  • Calculation and design-software - Free Download
  • Direct entry in a junction box possible